TBA Firefly™ Intubatt® Concrete Protection DTS Tested Systems for FRL 240/240/240
Standard Cellulosic Fire Exposure
Patent Pending
Minimum 100mm thick of Concrete Floor/Ceiling or Wall which has been designed to carry the applied loading @ ambient temperatures in accordance with AS3600:2018.
FLOOR/CEILING
DTS FRL240/240/240
1 layer of 50mm thick TBA Firefly™ Intubatt® fixed to the underside: Total System thickness 150mm
WALL (1 Way Fire) 1 layer of 50mm thick TBA Firefly™ Intubatt® fixed to the Fire Side Face: Total System thickness 150mm. DTS FRL240/240/240 |
WALL (2 Way Fire) 1 layer of 50mm thick TBA Firefly™ Intubatt® fixed to the Both Faces: Total System thickness 200mm DTS FRL240/240/240 |
DTS System FRL240/240/240 Tested in accordance with AS1530.4-2014 & Assessed in accordance with AS4072.1-2005 Warringtonfire Report No: FAS210074 RIR
This is a Report from an Accredited Testing Laboratory which meets Specification A2.3 Section 2 (c) of NCC2016 Amendment 1 (Including Prior Versions) & Schedule 5 Section 2 (c) of NCC2019 (Including Amendment 1) for determination of an FRL.
Complete Concrete Protection Zero Spalling witnessed during or after the Test
NEW BUILD
Benefits of the TBA Firefly™ Intubatt®/Concrete DTS Tested Systems:
RETROFIT CONCRETE FIRE UPGRADES
Current Potential Issues for some building stock in Australia:
We believe that this may be a serious non-compliance issue, due to the fact that Table 5.5.2(A) is sometimes overlooked in some Fire Engineered Solutions. This means that an FRP90/90/90 or FRP120/120/120 cannot be determined within an Alternate Solution (FES) in accordance with AS3600 if the floor slab is less than 200mm thick. Therefore the only route to compliance is via a DTS Tested System FRL.
The same applies for where the slab may be 200mm thick and designed for a building which originally only required an FRP90/90/90 or FRP120/120/120 or FRL90/90/90 or FRL120/120/120 which has since had a change of use and the FRP or FRL needs to be higher.
Solution:
Minimum 100mm thick Concrete designed to carry the applied loading @ ambient temperatures:
Install one layer of TBA Firefly™ Intubatt® to the underside of the slab to achieve a DTS FRL240/240/240 Horizontal separation Protection
Install one layer of TBA Firefly™ Intubatt® to one side of a concrete wall to achieve a DTS FRL240/240/240 Vertical Separation (1 way) Protection
Install one layer of TBA Firefly™ Intubatt® to both sides of a concrete wall to achieve a DTS FRL240/240/240 Vertical Separation (2 way) Protection
GROUP NUMBERS
If a Group Number is required for your application, the TBA Firefly™ Intubatt® is overlayed with TBA Firefly™ EKA-161 Non-combustible Sarking (Non-Breathable)
TEST METHOD AS ISO 9705-2003 (R2016)
Warringtonfire Reaction to Fire Test Report Number: RTF210386
RESULTS
ROOM CORNER BURN PRIOR TO TEST IMAGE
ROOM CORNER BURN DURING TEST IMAGE
ROOM CORNER BURN DURING TEST IMAGE
ROOM CORNER BURN POST TEST IMAGE